JSC Gran - manufacturer industrial quick freezing, cooling and heat exchanging equipment
About Products News Request Contacts Feedback Site map Russian version

Cooling machines MHV

Cooling machines MHV


Designed for keeping temperature till -18°C/-25°C in coldrooms and cold warehouses.


Type of
cooling unit
Cooling capacity by
Tevap= -25°C;
Tcond= +40°C, kW
Compressor Total power
consumption, kW
Overall dimensions
of cooling unit, mm
Weight of
cooling unit, kg
Coldroom volume,
m3 by -18°C
Power consumption
of electrical defrost, kW
Overall dimensions
of air cooler, mm
Weight of
air cooler, kg
Coldroom volume,
m3 by -25°C
MHV–5GS 4.83 “COPELAND”
ZF15K4E-TFD
3.9 1290x917x748 195 70*
4.4 1340x625x590 85 40*
MHV–6GS 5.69 “COPELAND”
ZF18K4E-TFD
4.4 1290x917x748 195 85*
5.6 1850x625x590 95 51*
MHV–7GS 7.05 “COPELAND”
ZF24K4E-TWD
5.8 1290x917x748 200 120*
6.4 1850x625x590 115 70*
MHV–10GS 9.60 “COPELAND”
ZF33K4E-TWD
7.9 1290x917x748 200 180*
10.0 2200x705x590 110 125*
MHV–14 14.59 “BITZER”
4N-12.2
9.7 2035x950x1205 341 320*
14.0 2800x705x590 130 210*
MHV–20 18.70 “BITZER”
4H-15.2
11.6 2735x950x1205 400 590*
19.8 3400x705x590 160 390*
MHV–23 24.20 “BITZER”
6J-22.2
13.5 2735x950x1205 465 820*
19.8 3400x705x590 160 500*
MHV–26 28.10 “BITZER”
6H-25.2
17.5 3435x950x1205 470 970*
23.4 3050x985x785 200 620*
MHV–30 32.50 “BITZER”
6G-30.2
20.0 3435x950x1205 480 1230*
29.9 3900x985x785 260 810*

* Present value is tentative and computed by average arguments of products storing.

Selection of cooling unit for each room deliver particularly.